The Files menu is accessible when the access locking switch is set to
the total unlocked, , position. Changes can only be made when
the motor is stopped.
The keypad display can store four drive controller configuration files.
A stored file can be downloaded into other drive controllers that have
the same horsepower and voltage rating and the same or earlier
version of firmware.
Cont. Stop StP
Controlled stop upon loss of
input phase.
No - MMS -
FRP
No
This function is only operational if the IPL parameter (Input
Phase Loss) is set to No. If IPL is set to Yes, leave StP set
to No. Possible choices:
• No: loss of input phase causes drive controller to trip
• MMS: Maintenance of DC bus: the DC bus is kept
energized by regenerating the kinetic energy from the
machine inertia, until the USF (Undervoltage) fault
appears.
• FRP: Following a ramp: deceleration following the
programmed ramp, either dEC or dE2 until the motor
stops or the USF (Undervoltage) fault appears. This
operation is not available on the ATV58•U09M2,
U18M2, U29M2 and U41M2.
RampNotFoll Sdd
This function can be accessed if
feedback via tachogenerator or
pulse generator is programmed.
Yes - No No
When enabled, it is used to lock the drive controller if a
speed error is detected (difference between the stator
frequency and the measured speed).
External fault ★ EPL
This configuration is used to
determine the response to an
external fault.
• Yes: immediate fault
• Stt: stop according to Stt
setting
Yes - Stt Yes
Table 21: 6—Fault Menu
Parameter Code Description
Adjustment
Range
Factory
Setting
★
This parameter is only available on 125–500 hp drive controllers.