VVDED397047USR6/03 Chapter 2—Menus
06/2003 6—Fault Menu
87
OutPhaseLoss OPL
Use to enable the output phase
loss protection.
Yes - No Yes
Set this parameter set to No if there is a contactor
between the drive controller and the motor, or if
multiple motors are used on the output of the drive
controller.
It may also be necessary to set OPL to No if the motor load
is less than 25% of the drive controller current rating (I
n
).
Input Phase Loss IPL
Allows activation of the Input
Phase Loss fault.
Yes - No Yes
This fault is not configurable on the following single phase
input drive controllers:
ATV58•U09M2
ATV58•U18M2
Disable IPL when operating the 208/230 Vac drive
controllers with single phase input.
ThermalProType tHt
This function defines the type of
thermal protection.
No - ACL -
FCL
ACL
Choices:
No: No motor thermal protection.
ACL: Self-cooled motor. The drive controller takes into
account a derating as a function of the rotation
frequency.
FCL: Force-cooled motor. The drive controller does not
take into account a derating as a function of the rotation
frequency.
Table 21: 6—Fault Menu
Parameter Code Description
Adjustment
Range
Factory
Setting
This parameter is only available on 125–500 hp drive controllers.