Chapter 2—Menus VVDED397047USR6/03
3—Drive Menu 06/2003
44
Mot.CosPhi CoS
Motor CosPhi, motor power
factor.
Set the CoS parameter to the
motor nameplate power factor.
0.5 to 1
depends
on drive
controller
rating
If the power factor is not provided on the nameplate or to
optimize the motor torque performance, use
the following
procedure to optimize the motor power factor setting.
Operate the motor with no load at a frequency equal to
nominal frequency / 2. Then adjust the CoS parameter
such that the measured motor voltage equals nominal
motor voltage / 2.
For example:
For a 460 Vac motor operating at 60 Hz, adjust the CoS
parameter to have 230 V at 30 Hz.
If motor voltage is less than 230 V, decrease CoS
parameter.
If motor voltage is more than 230 V, increase the CoS
parameter.
Table 11: 3—Drive Menu Parameters (continued)
Parameter Code Description
Adjustment
Range
Factory
Setting
[1]
Depending on the position of the 50/60 Hz switch. Ensure that the switch setting
matches the input frequency (see page 14).
[2]
I
n
= drive controller constant torque output current rating shown on the drive controller
nameplate.
[3]
The factory setting depends on the macro-configuration used: No for Material
Handling, Yes for General Use and Variable torque.
[4]
This parameter is not available on 125–500 hp drive controllers.
[5]
Refer to the drive controller instruction bulletin, VVDED397048US, for duty cycle
ratings of the drive controllers.
★ These parameters are available only with the I/O extension card installed.