5—I/O Menu 06/2003
72
parameters are automatically scaled by the command from the logic
input:
DC injection current
Brake release current
Nominal motor current
Second Torque Limit
Second Torque Limit reduces the maximum motor torque when the
logic input is closed (state set to 1). Use the 2—Adjust menu to
configure the percentage of torque.
Fault Reset
Fault reset erases a saved fault and resets the drive controller if the
cause of the fault has disappeared. Two types of reset are possible:
partial or total. This is set by the rSt parameter in the 6
Fault menu.
For a partial reset (rSt = RSP), the following faults are reset and
cleared from the display:
For a Total reset (rSt = RSG), all faults except SCF (Motor Short
Circuit) are overridden as long as the logic input assigned to Fault
Reset is closed.
input line overvoltage motor overload motor overheating
overbraking • network
communication fault
loss of RS-485 port
communication
motor phase loss loss of 4–20 mA drive overheating
ramp not followed external fault overspeed
CAUTION
MOTOR OVERHEATING
Repeated reset of the thermal state after a thermal overload can
result in thermal stress to the motor.
When faults occur, promptly inspect the motor and driven
equipment for problems (locked shaft, mechanical overload, etc.)
before restarting. Also check the power supplied to the motor for
abnormal conditions (phase loss, phase imbalance, etc.).
Failure to follow these instructions can result in equipment
damage.