This menu is only accessible when the access locking switch is in the
position. Modifications can only be made when the motor is
stopped.
Table 21: 6—Fault Menu
Parameter Code Description
Adjustment
Range
Factory
Setting
Auto Restart Atr
This function allows an
automatic restart of the drive
controller if the cause of the fault
has disappeared and a run
command is maintained.
Yes - No No
An automatic restart is possible after the following faults:
• OSF Input line overvoltage
• ObF overbraking
• OtF motor overheating (when the thermal sensor
resistance is less than 1500 ohms)
• LFF loss of 4–20 mA
• OLF motor overload (after the thermal state has
decreased below 100%)
• OPF motor phase loss
• OHF drive overheating (when the thermal state has
decreased below 70%)
• SLF loss of RS-485 port communication
• EPF external fault
• CnF network communication fault
When the Auto restart is active, the fault relay remains
energized. If the fault has disappeared, the drive controller
will attempt to restart the motor after a delay time set by
parameter tAr. If the drive controller remains faulted after
attempting the number of restarts set in the parameter nAr,
the fault relay de-energizes and the drive controller must
be reset by cycling power.
★
This parameter is only available on 125–500 hp drive controllers.
Menu
6
WARNING
AUTOMATIC RESTART
• Automatic restart can only be used for machines or installations that present no
danger in the event of automatic restarting, either for personnel or equipment.
• Equipment operation must conform with national and local safety regulations.
Failure to follow this instruction can result in death, serious injury, or equipment
damage.