4—Control Menu
The Control Menu is accessible when the access locking switch is in
the total unlock, , position. The parameters can only be modified
when the motor is stopped.
Table 12: 4—Control Menu: Keypad Display or 2- and 3-Wire
Control
Parameter Code Description
Adjustment
Range
Factory
Setting
TermStripCon. tCC
Configuration of the terminal
strip command: 2- or 3-wire
control.
2W - 3W 2W
NOTE: Modification of this parameter requires two
confirmations since it causes a reassignment of the logic
inputs. Shown below are the LI assignments when 3-wire
control is selected. See Table 3 on page 24 for the
assignments in 2-wire control. In 3-wire control, LI1 and LI2
cannot be reassigned.
Selecting 3-wire control inhibits the automatic restart
function.
3-wire control wiring example:
★ These I/O can be accessed if an I/O extension card has been installed.
[1]
For 125–500 hp drive controllers the factory setting are:
LI4 = Fault Reset; LI5 = ramp switching; LI6 = Not assigned
Menu
4
I/O
Material
Handling
General Use
Variable
Torque
LI1 STOP STOP STOP
LI2 Run forward Run forward Run forward
LI3 Run reverse Run reverse Run reverse
LI4 2 Preset speeds Jog
Reference
switching
[1]
LI5★ 4 Preset speeds Freewheel stop
Injection braking
[1]
LI6★ 8 Preset speeds Clear faults
Freewheel stop
[1]
24 V LI1 LI2 LIx
ATV58 TRX Terminal strip
LI1: Stop
LI2: Forward
LIx: Reverse