06/2003 5—I/O Menu
69
Preset Speeds
2, 4, or 8 speeds can be preset, requiring 1, 2, or 3 logic inputs,
respectively.
Table 19 shows how the logic inputs are configured for Preset
Speeds and the input states that activate them.
Figure 16: +Speed Timing Diagram (Selector Switches)
Forward
LSP
LSP
0
0
0
2nd action
1st action
aaa a a a a
bb
cc
d
Reverse
2nd action
1st action
Motor
Frequency
Table 19: Preset Speed Logic
2 Preset Speeds 4 Preset Speeds 8 Preset Speeds
Assign LIx to PS2. Assign LIx to PS2, then LIy to PS4.
Assign LIx to PS2, then LIy to PS4, then
LIz to PS8.
LIx Speed reference LIy LIx Speed reference LIz LIy LIx Speed reference
0 LSP + AI reference 0 0 LSP + AI reference 0 0 0 LSP + AI reference
1HSP 01SP2 001SP2
10SP3 010SP3
11HSP 011SP4
100SP5
101SP6
110SP7
111HSP
NOTE: To reassign the logic inputs to a function other than Preset Speeds, PS8 (LIz) must be cleared, then
PS4 (LIy), then PS2 (LIx).