Chapter 1—Overview VVDED397047USR6/03
Keypad Display 06/2003
16
Quick Configuration
First prepare your program settings using the forms beginning on
page 109.
Programming the Altivar 58 TRX controller is facilitated by internal
checks. It is recommended that you access the menus and program
in the following order. All of the steps are not obligatory in all cases.
1. Set the 50/60 Hz switch, (see page 14).
2. Select the language.
3. Select the macro-configuration.
NOTE: 125-500 hp drive controllers have only the variable torque
macro.
4. Select 2 or 3-wire control in the 4—Control menu.
5. Configure parameters in the 3—Drive Configuration menu.
6. Assign the I/O in the 5—I/O menu.
NOTE: If the selected Macro-Configuration is Hdg: Material
Handling, logic input LI4 must be reassigned or unassigned
before you can assign logic input LI3 to a new function.
If the Freewheel Stop / Run Permissive function is assigned to a
logic input, the drive controller will not start the motor unless
that logic input is connected to +24 V.
7. Configure parameters in the 4—Control menu.
8. Configure the switching frequency type in the 3—Drive
Configuration menu.
WARNING
UNINTENDED EQUIPMENT ACTION
Parameter changes affect drive controller operation.
Most parameter changes require pressing ENT. Some parameter
changes, such as reference frequency, take effect as soon as
you press the up or down arrow keys.
Read and understand this manual before using the keypad
display.
Failure to follow these instructions can result in death, serious
injury, or equipment damage.