ALTIVAR
58 Keypad Display VVDED397047US R8/01
Chapter 2 — Menus 08/01
74
© 1998–2001 Schneider Electric All Rights Reserved
PID Error
When configured for PID error, OPE, the analog output provides a signal
proportional to the PID regulator error as a percentage of the sensor
range being used for the PID feedback, (maximum feedback minus
minimum feedback). The minimum configured value, AOL, corresponds
to – 5%, while the maximum configured value, AOH, corresponds to +5%.
Zero corresponds to (minimum value + maximum value) / 2,
(AOL+AOH) / 2.
PID Integral Error
When configured for PID integral error, OPI, the analog output provides
a signal proportional to the PID integral error. The minimum configured
value, AOL, corresponds to the low speed setting, LSP, while the
maximum configured value, AOH, corresponds to the high-speed setting,
HSP.
Motor Power
When configured for motor power, OPR, the analog output provides a
signal proportional to power drawn by the motor. The minimum
configured value, AOL, corresponds to 0% of the motor nominal motor
power, while the maximum configured value, AOH, corresponds to 200%
of the motor nominal motor power.
Motor Thermal State
When configured for motor thermal state, THR, the analog output
provides a signal proportional to the thermal state of the motor calculated
by the drive controller. The minimum configured value, AOL, corresponds
to 0% of the motor thermal state, while the maximum configured value,
AOH, corresponds to 200% of the motor thermal state.
Drive Thermal State
When configured for drive thermal state, THD, the analog output provides
a signal proportional to the thermal state of the drive controller. The
minimum configured value, AOL, corresponds to 0% of the drive
controller thermal state, while the maximum configured value, AOH,
corresponds to 200% of the drive controller thermal state.