Using the Logic Inputs
Run Forward and Run Reverse
The logic input used for run reverse can be reassigned if the application
has only one rotation direction.
2-wire Control
In 2-wire control, run (forward or reverse) and stop are commanded by
the same logic input. When the logic input is closed (set to state 1), run is
commanded; when it is opened (set to state 0), stop is commanded. See
tCt on page 46 for more information.
3-wire Control
In 3-wire control, run (forward or reverse) and stop are commanded by
two different logic inputs. LI1 is always assigned to stop which is obtained
by opening LI1 (setting it to state 0). A pulse on the run input is saved until
the stop input is opened.
Whenever the drive controller is powered up or reset, the motor will only
run after resetting the Forward, Reverse, and DC injection inputs.
UNINTENDED EQUIPMENT OPERATION
LI1 has priority:
• If LI1 is closed while LI2 is active, the controller will respond to
LI1.
• If the LI1 input is lost while LI2 is active, the controller will
respond to LI2 and reverse directions.
The logic inputs must be programmed appropriately for the
application to prevent the motor from spinning in an unintended
direction.
Failure to follow this instruction can result in death, serious
injury, or equipment damage.