Mot.CosPhi
CoS
Motor CosPhi , motor power factor
Set the CoS parameter as provided on
the motor nameplate label.
If the power factor is not provided, or for
high performance applications, the
following procedure can be used to
optimize the motor power factor setting,
CoS.
0.5 to 1 depends on
drive
controller
rating
Operate the motor with no load at a frequency equal to nominal
frequency / 2. Then adjust the CoS parameter such that the
measured motor voltage equals nominal motor voltage / 2.
For example:
For a 460 Vac motor operating at 60 Hz,
adjust the CoS parameter to have 230 V at 30 Hz.
If motor voltage is less than 230 V, decrease CoS parameter.
If motor voltage is more than 230 V, increase the CoS parameter.
Auto Tuning
tUn
Initiates an autotune when the tUn
parameter is set to Yes. After the
autotune is complete, the display will
show “done”. No is displayed if the
autotune was not successful or
completed.
No - Yes No
No is also displayed if the motor rating is less than 25% of drive
controller I
n
rating or if multiple motors are connected. The CoS
parameter may need to be manually adjusted for optimum
performance.
This feature will not work if any logic inputs are activated. If
freewheel stop or fast stop are assigned to a logic input, they must
be in the high state to autotune.
When initiated, the drive controller pulses the connected motor,
measures, and stores specific motor stator resistance and
resistance of the conductors. This allows the drive controller to
provide better current regulation for better motor torque
performance. This can be initiated from the keypad display or by a
logic input assigned to this function.
Table 11: 3—Drive Menu Parameters (Continued)
Parameter Code Description
Adjustment
Range
Factory
Setting
[1]
Depending on the position of the 50/60 Hz switch. Ensure that the switch setting
matches the input frequency (see page 13).
[2]
I
n
= drive controller constant torque output current rating shown on the drive controller
nameplate.
[3]
The factory setting depends on the macro-configuration used: No for Material Handling,
Yes for General Use and Variable torque.
[4]
Refer to the drive controller instruction bulletin, VVDED397048US, for duty cycle ratings
of the drive controllers.
★ These parameters are available only with the I/O extension card installed.