VVDED397047US R8/01 ALTIVAR
58 Keypad Display
08/01 Chapter 2 — Menus
© 1998–2001 Schneider Electric All Rights Reserved
35
Additional Adjustment Parameters for Variable Torque
Table 9 lists the additional parameters that are accessible when the
macro-configuration is set to Variable Torque.
Table 9: 2—Additional Adjustment Parameters with Variable
Torque Macro-Configuration
Parameter Code Description
Adjustment
Range
Factory
Setting
DC Inj.Curr.- A
IdC
DC injection braking current level.
[1]
This parameter is accessible if a logic
input is assigned to DC injection
braking. After 30 seconds, IdC is
automatically set to 0.5 ItH if previously
set to a higher value.
0.10 to
1.36 of I
n
[1]
Varies
according
to drive
controller
size.
V/f Profile - %
PFL
Volts/Hertz Adjustment
This function is available in variable
torque mode and if the Energy
Economizer (Energy Savings) function
(nld) is disabled.
0 to 100% 20%
This parameter is useful in applications where the user wishes to
define the volts/hertz profile manually instead of having the drive
controller perform this function with the Energy Economizer
function.
[1]
I
n
= drive controller constant torque output current rating shown on the drive controller
nameplate.
Menu
2
NOTE: V/f Profile
is available only if
the energy savings
function (nld) is set
to No.