
VVDED397047US R8/01 ALTIVAR
58 Keypad Display
08/01 Chapter 2 — Menus
© 1998–2001 Schneider Electric All Rights Reserved
67
Table 20: Definition of PID Regulator Inputs and Adjustments
Input Code Range Description
PID setpoint —
The setpoint to the PID regulator can be provided from one of three
sources:
— via analog input, AI1 (AI2 and AI3 can be set to sum with AI1)
— via preset setpoints defined by logic inputs (as explained in the
table below)
— over a communication network
PID feedback —
The feedback to the PID regulator can be provided from AI2 (0–20 mA
signal) or AI3 (0–10 Vdc voltage signal).
Auto / Manual with
Manual Speed Input
PAU,
PIM
When the PID regulator is configured and a logic input is configured
for Auto / Manual, AI3 is the speed input in manual mode. The PID
regulator function is active in Auto mode. When the logic input is open,
(set to state 0), Auto mode is active and the PID regulator is active.
Manual mode is active when the logic input is closed, (set to state 1).
In manual mode AI3 is enabled and the drive controller responds
proportionally to the speed reference at AI3.
Preset setpoints Pr2, Pr4
0–100% of
process
maximum
Logic inputs can also be used to provide programmable setpoints.
Two or four preset setpoints require the use of one or two logic inputs
respectively.
PID Inversion PIC Yes/No
PID inversion permits an inverted response to the PID
setpoint signal.
(This is also referred to as reverse-acting.) If PIC = No, the motor
speed increases when the error is positive. If PIC = Yes, the motor
speed decreases when the error is positive.
PID proportional gain rPG 0.01–100
PID regulator proportional gain adjusts the scaling of the
PID setpoint
signal.
PID integral gain rlG 0.01–100 s PID regulator integral gain adjustment.
Low pass feedback
filter
PSP 0–10 s
PSP can be used to dampen the feedback signal. If PSP is set to zero,
the ACC and dEC ramps are active. If PSP is > 0, the AC2 ramp is
active. Adjustment of AC2 can be used to refine the response of the
PID loop. The dEC ramp is used on deceleration.
PID Feedback scaling FbS 1.0–100
PID feedback scaling allows adjustment of the maximum value of the
PID feedback signal so that it corresponds to the maximum value of
the PID regulator speed reference.
2 preset setpoints 4 preset setpoints
Assign: LIx to Pr2 Assign: LIx to Pr2, then LIy to Pr4
LIx Reference LIy LIx Reference
0
1
Analog reference
Process max.
0
0
1
1
0
1
0
1
Analog reference
PI2 (adjustable)
PI3 (adjustable)
Process max.
Komentarze do niniejszej Instrukcji