Schneider Electric Altivar 58 VW3-A58101 Instrukcja Użytkownika Strona 42

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 112
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 41
ALTIVAR
58 Keypad Display VVDED397047US R8/01
Chapter 2 Menus 08/01
42
© 19982001 Schneider Electric All Rights Reserved
Type of stop
Stt
Type of stop:
When a stop is requested, the type of
STNFST
NSTDCI
STN
stop is activated until the FFt threshold (2Adjust menu) is reached.
Below this threshold, freewheel stop is activated.
Stn: On decel ramp
Fst: Fast stop
Nst: Freewheel stop
Dci: DC injection stop
Ramp Type
rPt
Defines the type of acceleration and
deceleration ramps.
LIN: linear S: S ramp U: U ramp
LIN - S - U LIN
Table 11: 3Drive Menu Parameters (Continued)
Parameter Code Description
Adjustment
Range
Factory
Setting
[1]
Depending on the position of the 50/60 Hz switch. Ensure that the switch setting
matches the input frequency (see page 13).
[2]
I
n
= drive controller constant torque output current rating shown on the drive controller
nameplate.
[3]
The factory setting depends on the macro-configuration used: No for Material Handling,
Yes for General Use and Variable torque.
[4]
Refer to the drive controller instruction bulletin, VVDED397048US, for duty cycle ratings
of the drive controllers.
These parameters are available only with the I/O extension card installed.
Menu
3
NOTE: This
parameter, Stt,
cannot be
accessed if the
R2 relay or a
logic output is
assigned to the
BLC: Brake
Logic function.
50/60
Time
0
1/5
ACC/deC
ACC/deC
Motor
Frequency (Hz)
1/5
ACC/deC
S ramp
fn
f (Hz)
t
fn
f (Hz)
t
T1
T1
U Ramp
Acc
T1 = 1/Acc
Dec
T1 = 1/Dec
Przeglądanie stron 41