VVDED397047US R8/01 ALTIVAR
58 Keypad Display
08/01 Chapter 2 Menus
© 19982001 Schneider Electric All Rights Reserved
43
DecRamp Coeff
dCF
Coefficient for reducing the
deceleration ramp time when a logic
input has been assigned to the Fast
Stop function.
For example:
If dec=20 s, setting dCF to 2 results in a
10 s dec ramp setting.
1 to 10 4
Trq.Limit1 -%
tLI
Torque limit allows limitation of the
maximum motor torque.
0 to 200%
torque
200%
Int.I Lim -A
CLI
Current limit used to limit the maximum
motor heating.
0 to 1.36 of
I
n
[2]
1.36 of I
n
[2]
Auto DC Inj.
AdC
Allows deactivation of automatic DC
injection at stop.
No - Yes Yes
Mot P Coef.
PCC
Defines the ratio between the nominal
drive controller power and the motor
with the lowest power rating when a
logic input is assigned to the motor
switching function (see page 62).
0.2 to 1 1
Sw. Freq. Type
SFt
Allows selection of the type of switching
frequency.
LF allows adjustment between 0.5
and 4 kHz using the SFr parameter.
LF - HF1 -
HF2
[4]
LF
HF1 and HF2 allow adjustment between 4 and 16 kHz:
HF1 is for applications with a low duty cycle, without derating
the drive controller. If the drive controller thermal state goes
above 95%, the switching frequency automatically goes to
2 or 4 kHz (depending on rating). When the thermal state returns
to 70%, the switching frequency returns to the set value.
HF2 is for machines with a high duty cycle with derating of the
drive controller by one power rating. The drive parameters
(current limit, thermal current, etc.) are automatically scaled.
Sw Freq -kHz
SFr
Selection of switching frequency. The
range depends on the SFt parameter.
The maximum operational frequency
(tFr) is limited depending on the
switching frequency:
LF: 0.5-1-2-
4 kHz
HF1 or HF2:
4- 8-12-16
kHz
[4]
LF: 4 kHz
HF1 or HF2:
(depending
on controller
rating)
Table 11: 3Drive Menu Parameters (Continued)
Parameter Code Description
Adjustment
Range
Factory
Setting
[1]
Depending on the position of the 50/60 Hz switch. Ensure that the switch setting
matches the input frequency (see page 13).
[2]
I
n
= drive controller constant torque output current rating shown on the drive controller
nameplate.
[3]
The factory setting depends on the macro-configuration used: No for Material Handling,
Yes for General Use and Variable torque.
[4]
Refer to the drive controller instruction bulletin, VVDED397048US, for duty cycle ratings
of the drive controllers.
These parameters are available only with the I/O extension card installed.
Menu
3
NOTE: DecRamp
Coeff is only
available if fast
stop is enabled.
NOTE: Mot P
Coef. is only
available if
motor switching
is enabled.
NOTE: Modifying
SFt causes the
following
parameters to
revert to factory
settings:
3Drive Menu:
nCr, CLI, SFr, nrd
2Adjust Menu:
itH, IdC, Ibr, Ctd