Functions (continued)
Altivar
®
12
variable speed drives
Quick start
The quick start function aims to overcome the problems associated with the high
regulation gains that are necessary at start-up but inappropriate for regulation.
The drive accelerates linearly on a ramp (ACC) until its speed reaches the
conguredquickstartthreshold(SFS).
Once it reaches this threshold (SFS), PID regulation begins.
ACC
SFS
HSP
Quick start
Variable pump frequency
HSP: High speed
SFS: Quick start threshold
ACC: Acceleration ramp time
Automatic restart on underload and overload faults
Generally, the user can set a parameter to activate automatic restarting after a fault,
if the cause(s) of the fault no longer exist(s).
In the case of underload and overload faults, a delay which can be set between 1 s
and 6 min 16 s can be used to delay the restart.
PID reference adjustment range for the end user
ThisfunctionallowstheendusertoadjustthePIDregulatorreferencetoincreaseor
reducetherateofow.
AdjustmentbytheuseriseitherbymodifyingthePIDregulatorreferenceparameter,
or by manual control of the navigation button, accessible on the drive's front panel.
The installer has access to two PID reference limit parameters, which can be used to
deneauser'srangeofaction.
Incompatible functions
Application functions can be assigned to the same logic input, in which case one
logic input enables a number of functions (for example, direction of operation and
ramp time switching).
A check must be carried out to ensure that the functions are compatible:
Direction of operation and 2-wire control: Forward operation can only be
assigned to LI1.
Direction of operation and 3-wire control: Forward operation can only be
assigned to LI2.
Automatic restart:Thisfunctionrequiresthecongurationof2-wirelevelcontrol.
Changingthecontroltypecongurationdeactivatesautomaticrestarting.
Automatic catching of a spinning load with speed detection: Incompatible with
continuousstandstillDCinjection.Conguringthisfunctiondeactivatesautomatic
catching of a spinning load.
Introduction:
page 8
Specications:
page 10
References:
page 14
Dimensions:
page 18
Connections:
page 22
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com