Drives with heatsink
Motor Line supply Altivar 12
Power
indicated
on rating
plate (1)
Max. line
current
(3)
Apparent
power
Max.
prospec-
tive line
Isc
Maximum
continuous
output
current
(In) (1)
Maximum
transient
current for
60 s
Dissipated
power at
maximum
output
current
(In) (1)
Reference Weight
(2)
at U1 at U2 at U2 at U2
kW HP A A kVA kA A A W kg
Single-phase supply voltage: 100 to 120 V 50/60 Hz (4)
0.18 0.25 6 5 0.6 1 1.4 2.1 18 ATV12H018F1 (5) 0.700
0.37 0.5 11.4 9.3 1.1 1 2.4 3.6 29 ATV12H037F1 0.800
0.75 1 18.9 15.7 1.9 1 4.2 6.3 48 ATV12H075F1 1.300
Single-phase supply voltage: 200 to 240 V 50/60 Hz (4) (6)
0.18 0.25 3.4 2.8 0.7 1 1.4 2.1 18 ATV
12H018M2 (5) (7)
0.700
0.37 0.55 5.9 4.9 1.2 1 2.4 3.6 27 ATV12H037M2 (7) 0.700
0.55 0.75 8 6.7 1.6 1 3.5 5.3 34 ATV12H055M2 (7) 0.800
0.75 1 10.2 8.5 2 1 4.2 6.3 44 ATV12H075M2 (7) 0.800
1.5 2 17.8 14.9 3.6 1 7.5 11.2 72 ATV12HU15M2 (8) 1.400
2.2 3 24 20.2 4.8 1 10 15 93 ATV12HU22M2 (8) 1.400
Three-phase supply voltage: 200 to 240 V 50/60 Hz (4)
0.18 0.25 2 1.7 0.7 5 1.4 2.1 16 ATV12H018M3 (5) 0.700
0.37 0.55 3.6 3 1.2 5 2.4 3.6 24 ATV12H037M3 0.800
0.75 1 6.3 5.3 2.2 5 4.2 6.3 41 ATV12H075M3 0.800
1.5 2 11.1 9.3 3.9 5 7.5 11.2 73 ATV12HU15M3 1.200
2.2 3 14.9 12.5 5 5 10 15 85 ATV12HU22M3 1.200
3 – 19 15.9 6.6 5 12.2 18.3 94 ATV12HU30M3 2.000
4 5 23.8 19.9 8.3 5 16.7 25 128 ATV12HU40M3 2.000
Drives on a base plate
Single-phase supply voltage: 100 to 120 V 50/60 Hz (4)
0.18 0.25 6 5 0.6 1 1.4 2.1 18 ATV12H018F1 (5) 0.700
– – 11.4 9.3 1.1 1 2.4 3.6 29 ATV12P037F1
(9)
0.700
Single-phase supply voltage: 200 to 240 V 50/60 Hz (4) (6)
0.18 0.25 3.4 2.8 0.7 1 1.4 2.1 18 ATV
12H018M2 (5) (7)
0.700
– – 5.9 4.9 1.2 1 2.4 3.6 27 ATV12P037M2
(9)
0.700
– – 8 6.7 1.6 1 3.5 5.3 34 ATV12P055M2
(9)
0.700
– – 10.2 8.5 2 1 4.2 6.3 44 ATV12P075M2
(9)
0.700
Three-phase supply voltage: 200 to 240 V 50/60 Hz (4)
0.18 0.25 2 1.7 0.7 5 1.4 2.1 16 ATV12H018M3 (5) 0.700
– – 3.6 3 1.2 5 2.4 3.6 24 ATV12P037M3
(9)
0.700
– – 6.3 5.3 2.2 5 4.2 6.3 41 ATV12P075M3
(9)
0.700
– – 11.1 9.3 3.9 5 7.5 11.2 73 ATV12PU15M3
(9)
1.000
– – 14.9 12.5 5 5 10 15 85 ATV12PU22M3
(9)
1.000
– – 19 15.9 6.6 5 12.2 18.3 94 ATV12PU30M3
(9)
1.600
– – 23.8 19.9 8.3 5 16.7 25 128 ATV12PU40M3
(9)
1.600
(1) These values are given for a nominal switching frequency of 4 kHz, for use in continuous operation.
If operation above 4 kHz needs to be continuous, the nominal drive current should be derated by 10% for 8 kHz, 20% for 12 kHz
and 30% for 16 kHz.
The switching frequency can be set between 2 and 16 kHz for all ratings.
Above 4 kHz, the drive will reduce the switching frequency automatically in the event of an excessive temperature rise.
See the de-rating curves in the User Manual, available on our website at "www.schneider-electric.us".
(2) Weight of product without packaging.
(3) Typical value for the indicated motor power and for the maximum prospective line Isc.
(4) Min. (U1) and max. (U2) nominal supply voltage: 100 (U1) to 120 V (U2), 200 (U1) to 240 V (U2).
(5) Due to the poor heat dissipation, the ATV12H018pp drive is only supplied as a base plate version.
(6) Drive supplied with category C1 integrated EMC lter. This lter can be disconnected.
(7) Available in lots of 14: add TQ at the end of the reference. For example, ATV12H018M2 becomes ATV12H018M2TQ.
(8) Available in lots of 7: add TQ at the end of the reference. ATV12HU22M2 becomes ATV12HU22M2TQ.
(9) To size the ATV12Pppppp drive correctly, see the specic manual for the Altivar
®
12 base plate version, available on our
website at “www.schneider-electric.us”.
References
Altivar
®
12
variable speed drives
Drives with heatsink, drives on a base plate
Introduction:
page 8
Specications:
page 10
Dimensions:
page 18
Connections:
page 22
Functions:
page 26
ATV12H018M2
ATV12H075M2
ATV12HU40M3
ATV12PU22M3
ATV12HU15M2TQ (8)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Komentarze do niniejszej Instrukcji