Functions (continued)
Altivar
®
12
variable speed drives
Pump-specic application functions
Themainobjectivehereistocontrolacompletepumpinginstallationusingasingle
Altivar
®
12drivebyensuringconstantpressureinthesystemwhatevertheowrate.
The Altivar 12 has 11 functions designed for water pumping applications:
b Control in single variable mode
b Control in single variable mode with auxiliary pump
b Underload detection
b Overload detection
b Sleep
b Wake-up
b PID feedback supervision
b No-load operation detection
b Quick start
b Automatic restart on underload and overload faults
b PIDreferenceadjustmentrangefortheenduser
Control in single variable mode
The system is operated using a single variable speed pump (
1
).
A PID regulator controls the variable speed pump.
A pressure sensor provides the “PID feedback” information required for system
feedback.
Control in single variable mode with auxiliary pump
Thesystemisoperatedusingaxedspeedpump,calledtheauxiliarypump,anda
variablespeedpump,whichisunabletoprovidethefullowrangerequiredonits
own (
2
).
The auxiliary pump's starting and stopping are controlled by logic output LO+
according to the PID regulator output (variable pump frequency reference) with a
hysteresis effect as shown in the diagram below (
3
).
Auxiliary pump starting (
4
)
If the variable pump control frequency exceeds the threshold (FOn) for longer than a
time period (tON), the auxiliary pump is put into operation (1). The variable pump
reference decreases linearly until it reaches the threshold (FOF).
In order to reduce the effect of overpressure caused by starting of the auxiliary
pump, the deceleration time of the variable pump (rOn) must be set to the time that
the auxiliary pump takes to reach its nominal speed.
Auxiliary pump stopping (
5
)
Conversely, if the variable pump control frequency falls below the threshold (FOF)
for a period (tOF), the auxiliary pump is stopped (2) and the variable pump reference
increases linearly until it reaches the threshold (FOn). The acceleration time (rOF)
is set to the stopping time of the auxiliary pump in order to minimize the effect of
underpressure.
3
1
2
FOF
FOn
HSP
Single variable mode with auxiliary pump: hysteresis
Installationowrate
Variable pump frequency (Hz)
3
1
FOF
FOn
t
tOn rOn
Auxiliary pump start
Variable pump frequency (Hz)
4
FOF
FOn
t
tOF
rOF
2
Auxiliary pump stop
Variable pump frequency (Hz)
5
Auxiliary pump starting1
Auxiliary pump stopping2
Frequencyrangecorrespondingtotheauxiliarypumpowrate3
FOn: Starting frequency of the auxiliary pump
FOF: Stopping frequency of the auxiliary pump
Introduction:
page 8
Specications:
page 10
References:
page 14
Dimensions:
page 18
Connections:
page 22
Single variable mode
1
Single variable mode with auxiliary pump
2
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com