Schneider Electric Multi-Loader Dokumentacja Strona 26

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 40
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 25
1
2
3
4
5
6
7
8
9
10
24
Applications
The proposed combinations can:
b Protect people and equipment (when a short-circuit occurs)
b Maintain protection upstream of the drive in the event of a short-circuit on the
power stage
Two types of combination are possible:
b Drive + circuit-breaker: Minimum combination
b Drive + circuit-breaker + contactor: Minimum combination with contactor when a
control circuit is needed
Motor starters
Standard
power
ratings of
three-phase
4-pole
50/60 Hz
motors
(2)
Variable speed
drive
Combination with control circuit
(circuit-breaker + contactor)
Minimum combination
(circuit-breaker only)
TeSys
contactor
(1)
TeSys
®
motor
circuit-breaker
(3)
Operating
range or
rating
Maximum
short-circuit
current Icu
Modular
circuit-breaker
(4)
kW HP A kA
M1 A1 Q1 KM1
Single-phase supply voltage: 100 to 120 V 50/60 Hz (5)
0.18 0.25 ATV12H018F1 GV2ME14 6 to 10 > 100 LC1K09
GV2L10 6.3 > 100
2-pole C60N 10 10
0.37 0.5 ATV12p037F1 GV2ME16 9 to 14 > 100 LC1K12
GV2L16 14 > 100
2-pole C60N 16 10
0.75 1 ATV12H075F1 GV2ME21 17 to 23 50 LC1D25
GV2L22 25 > 50
2-pole C60N 20 10
Single-phase supply voltage: 200 to 240 V 50/60 Hz (5)
0.18 0.25
ATV12H018M2
GV2ME08 2.5 to 4 > 100 LC1K09
GV2L08 4 > 100
2-pole C60N 6 10
0.37 0.55 ATV12p037M2 GV2ME14 6 to 10 > 100 LC1K09
GV2L10 6.3 > 100
2-pole C60N 10 10
0.55 0.75 ATV12p055M2 GV2ME14 6 to 10 > 100 LC1K09
GV2L14 10 > 100
2-pole C60N 10 10
0.75 1 ATV12p075M2 GV2ME16 9 to 14 > 100 LC1K12
GV L16 14 > 100
2-pole C60N 16 10
1.5 2 ATV12HU15M2 GV2ME21 17 to 23 50 LC1D18
GV2L20 18 > 100
2-pole C60N 20 10
2.2 3 ATV12HU22M2 GV2ME32 24 to 32 50 LC1D25
GV2L22 25 50
2-pole C60N 32 10
(1) For a complete list of references for TeSys contactors, please refer to the "Motor starter
solutions - Control and protection components" and "Motor starters up to 150 A" catalogs or visit
"www.schneider-electric.us".
(2) Motor power indicated for combination with an ATV12Hppppp drive with the same rating. For
combination with an ATV12Pppppp drive, refer to the specic manual for the Altivar
®
12 base
plate version, available on our website at “www.schneider-electric.us”.
(3) TeSys motor circuit-breakers:
- GV2MEpp: Thermal magnetic motor circuit-breakers with pushbutton control
- GV2Lpp: Magnetic motor circuit-breakers with control by rotary knob
(4) 2-pole C60N modular circuit-breaker
(5) Can be integrated in devices connected to a power socket:
- If the line current is y 16 A, connection to a single-phase power socket, 10/16 A 250 V z
- If the line current is > 16 A, connection to a single-phase power socket conforming to standard
IEC 60309
Combinations for
customer assembly
Altivar
®
12
variable speed drives
Motor starters: Single-phase supply voltages
100 to 120 V and 200 to 240 V
Introduction:
page 8
Specications:
page 10
References:
page 14
Dimensions:
page 18
Connections:
page 22
Motor starter with single-phase power supply
2
4
1
3
W/T3
U/T1
V/T2
R/L1
S/L2/N
U1
W1
V1
M1
3
2
4
2
4
6
1
3
5
1
3
Q1:
C60N2P
KM1:
TeSys LC1ppp
(if control circuit)
A1:
ATV12ppppF1,
ATV12ppppM2
Q1:
GV2pppp
M1:
200..240 V three-phase
asynchronous motor
or
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Przeglądanie stron 25
1 2 ... 21 22 23 24 25 26 27 28 29 30 31 ... 39 40

Komentarze do niniejszej Instrukcji

Brak uwag