Step 4: Wiring the Inverter
975-0239-01-01 2–13
This manual for use by qualified personnel only
Torque Values for the Xantrex XW Series Inverter/Charger
Torque Values for the Xantrex XW Power Distribution Panel
Table 2-4 Torque Values for AC Wiring (AC Terminals and Ground Bar)
Wire Size Torque Value
AWG In-lb N-m
14–10 35 4.0
8404.5
6–4 45 5.1
Table 2-5 Torque Values for the Chassis Ground Lug
Wire Size Torque Value
AWG In-lbs N-m
6-4 45 5.1
3-2 50 5.6
Table 2-6 Torque Values for the Inverter Battery Terminals
Torque Value
Ft-lbs N-m
15 20.4
Table 2-7 Torque Values for AC Disconnects and AC Breakers
Wire Size Torque Value
AWG In-lb N-m
16–10 45 5.1
8455.1
6–4 45 5.1
Table 2-8 Torque Values for the Ground Bus, AC Neutral Bus, DC Negative Bus,
and DC Positive Bus in the Xantrex XW Power Distribution Panel
Wire Size Torque Value
AWG In-lbs N-m
14 - 10 35 4.0
8404.5
6 - 4 45 5.1
3 - 2/0 50 5.6