Inverter/Charger Installation
2–12 975-0239-01-01
This manual for use by qualified personnel only
Battery cable
length
Runs should be kept as short as practical. Length should not exceed 10 feet
(3 m). For best performance, the positive and negative cables should run
alongside each other. Avoid cable loops.
Battery cable lugs Battery cables must have crimped copper compression lugs or crimped and
soldered copper compression lugs. Soldered connections alone are not
acceptable. Lugs must be rated for use with fine-stranded cable.
Overcurrent
protection
For safety and compliance with regulations, battery overcurrent protection is
required. Fuses and disconnects must be sized to protect the wiring in the
system and are required to open before the wire reaches its maximum current
carrying capability.
Terminal covers Color-coded snap-on DC terminal covers are provided to prevent accidental
contact with the terminals. Terminal covers are required for all installations, even
if a Xantrex XW Conduit Box is used. It is also recommended that the shank of the
ring terminals (cable lugs) be covered with heat shrink or some other form of
insulation.
Table 2-2 Recommended Battery Cable Size Versus Length
Inverter Model Up to 5 Feet (1.5 m) (90°C wire)
Up to 10 Feet (3 m)
(90°C wire)
Xantrex XW4024 #4/0 AWG (120 mm
2
) #4/0 AWG (120 mm
2
)
Xantrex XW4548 #2/0 AWG (70 mm
2
) #4/0 AWG (120 mm
2
)
Xantrex XW6048 #4/0 AWG (120 mm
2
) #4/0 AWG (120 mm
2
)
Important: The NEC/CEC requires both overcurrent protection and a disconnect
switch for residential and commercial electrical systems. These items are not
supplied as part of the inverter, but are included in the Xantrex XW Power
Distribution Panel.
Table 2-3 Battery Cable (in Conduit) to Maximum Breaker/Fuse Size
Cable Size Required Maximum Breaker/Fuse Size
#2/0 (00) AWG 175 amps
#4/0 (0000) AWG 250 amps