63230-507-201A1 Power Meter 750
03/2007 Section 6—Alarms
© 2007 Schneider Electric All Rights Reserved
27
SECTION 6— ALARMS
ALARMS
ABOUT ALARMS The PM750 can detect 15 pre-configured alarms. A complete list of alarm
configurations is described in Table 6– 1. All alarms can be configured with
the following values when using the display except that digital alarms have a
fixed pickup and dropout magnitude:
• Enable—disable (default) or enable.
• Pickup Magnitude—For digital alarms off-to-on (1), on-to-off (0)
• Pickup Time Delay (0-32767 seconds)
• Dropout Magnitude—For digital alarms off-to-on (0), on-to-off (1)
• Dropout Time Delay (0-32767 seconds)
Values that can also be configured over communications are:
• Alarm Type
• Test Register (reading)
• Alarm Label
The
! icon appears in the upper-right corner of the power meter display
when an alarm is active.
ALARM CONDITIONS AND ALARM
NUMBERS
Table 6– 1 lists the pre-configured alarms by alarm number. For each alarm
condition, the following information is provided.
• Alarm No.—a position number indicating where an alarm falls in the list.
• Alarm Description—a brief description of the alarm condition
• Abbreviated Display Name—an abbreviated name that describes the
alarm condition, but is limited to 16 characters that fit in the window of
the power meter’s display.
• Test Register—the register number that contains the value that is used
as the basis for a comparison to alarm pickup and dropout settings. This
value is an integer, and the evaluation produces an absolute value.
Table 6– 1: List of Default Alarms by Alarm Number
Alarm
Number
Alarm
Description
Abbreviated
Display Name
Test
Register
Standard Speed Alarms (1 Second)
01 Over Kilowatt OVER KW 4006
02 Over Kilovolt-Ampere OVER KVA 4007
03 Over Kilovolt-Ampere-Reactive OVER KVAR 4008
04 Under Power Factor UNDER POWER FAC 4009
05 Over Voltage L-L OVER U 4010
06 Over Voltage L-N OVER V 4011
07 Under Voltage L-L UNDER U 4010
08 Under Voltage L-N UNDER V 4011
09 Over Current OVER CURRENT 4012
10 Over Frequency OVER FREQUENCY 4013
11 Under Frequency UNDER FREQUENCY 4013
12 Over THD Current OVER THD CURRENT 4045
13 Over THD Voltage OVER THD VOLTAGE 4052
Komentarze do niniejszej Instrukcji