63230-507-201A1 Power Meter 750
03/2007 Section 3—Operation
© 2007 Schneider Electric All Rights Reserved
9
Set Up Demand Current and Power
Set Up the Passwords
1. In SETUP mode, press ###: until DMD
(demand) is visible.
2. Press DMD (demand setup).
3. Enter the MIN (demand interval in
minutes) for I (current): 1 to 60.
4. Press OK.
5. Enter the MIN (demand interval in
minutes) for P (power): 1 to 60.
6. Press OK.
7. Enter the SUB-I (number of sub-
intervals) for P: 1 to 60.
8. Press OK
to return to the SETUP
MODE screen.
NOTE: The calculation method used for
current is Thermal.
NOTE: The calculation method used for
power is based on SUB-I as follows:
• 0 = sliding block
• 1= block
• >1 = rolling block (The SUB-I value must
divide evenly into the MIN value. For
example, if MIN is 15, SUB-I can be 3,
5, or 15. If you selected 3, you would
have 3 sub-intervals at 5 minutes each.
$%-!.$3%450
/+
-).
-3%#
+6!2(
-3%#
-).
35")
0
0
)
1. In SETUP mode, press ###: until PASSW
(password) is visible.
2. Press PASSW.
3. Enter the SETUP password.
4. Press OK.
5. Enter the RESET (password to reset the
power meter) password.
6. Press OK to return to the SETUP MODE
screen.
<-
PASSWORD SETUP
1; + OK
00000
00000
00000
DIAG.
RESET
MIN.MX
&
00000
SETUP