Power Meter 750 63230-507-201
Section 5—Input/Output Capabilities 03/2007
© 2007 Schneider Electric All Rights Reserved24
Calculating the Kilowatt-hour- Per-Pulse
Value
This section shows an example of how to calculate kilowatt-hours per pulse.
To calculate this value, first determine the highest kW value you can expect
and the required pulse rate. In this example, the following assumptions are
made:
The metered load should not exceed 1600 kW.
About two KY pulses per second should occur at full scale.
Step 1: Convert 1600 kW load into kWh/second.
Step 2: Calculate the kWh required per pulse.
Step 3: Round to the next option (0.01, 0.1, 1, 10, 100, 1000, 10,000).
(1600 kW)(1 Hr) 1600 KWh=
(1600 kWh)
1 hour
-------------------------------
X kWh
1 second
------------------------=
(1600 kWh)
3600 seconds
--------------------------------
X kWh
1 second
---------------------=
X 1600/3600 0.444 kWh/second==
0.444 kWh/second
2 pulses/second
--------------------------------------------- 0.2222 kWh/pulse=
Ke 1 kWh/pulse=