Schneider Electric K series Instrukcja Użytkownika Strona 56

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 55
PM1000 Series Power Meters PLSED309039EN
Chapter 6 Data Communication 08/2010
56
© 2010 Schneider Electric. All rights reserved.
Y phase RMS Block:
Function Code: 03H Read
Number of registers: 20
No scaling required
Read as block only
Table 6-7: Y phase RMS block
Parameter
Description
Address
Type
PM1200
VA2
Apparent power, phase 2
3061
Float
W2
Active power, phase 2
3063
Float
VAR2
Reactive power, phase 2
3065
Float
PF2
Power factor, phase 2
3067
Float
V23
Voltage phase 2 to phase 3
3069
Float
V2
Voltage phase 2 to neutral
3071
Float
A2
Current, phase 2
3073
Float
F2
Frequency, Hz
3075
Float
Reserved
Reserved
3077
Long
Intr2
Number of interruption
3079
Long
B phase RMS Block:
Function Code: 03H Read
Number of registers: 20
No scaling required
Read as block only
Table 6-8: B phase RMS block
Parameter
Description
Address
Type
PM1200
VA3
Apparent power, phase 3
3091
Float
W3
Active power, phase 3
3093
Float
VAR3
Reactive power, phase 3
3095
Float
PF3
Power factor, phase 3
3097
Float
V31
Voltage phase 3 to phase 1
3099
Float
V3
Voltage phase 3 to neutral
3101
Float
A3
Current, phase 3
3103
Float
F3
Frequency, Hz
3105
Float
Reserved
Reserved
3107
Long
Intr3
Number of interruption
3109
Long
Przeglądanie stron 55