Schneider Electric K series Instrukcja Użytkownika Strona 39

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 38
PLSED309039EN PM1000 Series Power Meters
08/2010 Chapter 5 Installation
© 2010 Schneider Electric. All rights reserved.
39
Auxiliary Supply (Control Power)
The PM1000 power meter requires a single-phase AC/DC auxiliary (control)
power supply to powerup its internal electronic circuitry. External surge
suppressors are necessary in the auxiliary supply circuit for proper operation
during extreme surge conditions, where the voltage surges exceed the
auxiliary supply limits (e.g.,rural areas and outlying areas prone to lightning
strikes).
Range:
44 to 277 VAC/DC.
Burden (load) < 3 VA at 240 V.
The control power may be derived from the voltage signals.
If you have a 440 V 3-wire delta system and a reliable neutral is not
available, use a 440 V: 240 V supply transformer to provide the standard
240 V auxiliary supply.
NOTE: It is much easier to set up the meter before you mount the meter on the panel. See
“Quick setup” on page 17 for more information.
PTs (VTs) and CTs
Large electrical installations have high voltages and currents, which may
exceed the direct connection rating of the power meter. In this case,
potential transformers (PTs) and current transformers (CTs) are used to
precisely step down or reduce the voltage and current levels to suit the
power meter rating. Potential transformers usually have a full scale output of
110 VAC RMS line-line and current transformers usually have a full scale
output of 5 A or sometimes 1 A.
The PTs (VTs) and CTs must be planned, installed, and tested by a qualified
electrical contractor before wiring the power meter. The accuracy of the
measurement also depends on the accuracy and phase angle error of the
PTs (VTs) and CTs. Instrument class 1 or better PTs and CTs are
recommended. Do not use protection class (10P10, etc.) CTs to feed the
power meters; they have poor accuracy and phase characteristics.
Ensure that the CT primary rating has been selected so that your normal
load variation lies between 40% and 80% of its full scale. If your CT is over-
rated, say if the load is always less than 10% of the CT primary rating,
accuracy suffers. On the other hand, if the CT is under-rated, then you may
exceed its full scale and burn out both the CT and the power meter.
PT (VT), CT Wiring
The PTs (VTs) and CTs must have adequate VA rating to support the
burden (loading) on the secondaries. You may want to support the auxiliary
supply burden from one of the PTs (VTs). CT wiring can impose additional
burden (loading) on the CT. For example, if the CT has a 5 A secondary and
the wire resistance is 1.0 Ω, then the CT has to support an additional burden
of 5 VA. If the wiring distance from the CT secondary is greater than stated
in Table 5-5 on page 41, then the CT could get over-burdened and give
large errors. Choosing a 1 A CT secondary can reduce this error. The CT
secondary value must be user programmed into the power meter.
The power meters should be conveniently located for easy connections of
voltage (PT), current (CT) signals, and auxiliary (control) supply.
NOTE: The power meters user programmable PT and CT primary or secondary settings, may
be utilized to Calibrate out the PT and CT amplitude error, for improved accuracy.
Przeglądanie stron 38
1 2 ... 34 35 36 37 38 39 40 41 42 43 44 ... 80 81

Komentarze do niniejszej Instrukcji

Brak uwag