Schneider Electric K series Instrukcja Użytkownika Strona 54

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 53
PM1000 Series Power Meters PLSED309039EN
Chapter 6 Data Communication 08/2010
54
© 2010 Schneider Electric. All rights reserved.
Parameter
Description
Address
Type
PM1200
Metering - Frequency
F
Frequency, Hz
3915
Float
Power Quality
THD
%V1
Voltage THD, phase 1
3861
Float
%V2
Voltage THD, phase 2
3863
Float
%V3
Voltage THD, phase 3
3865
Float
%A1
Current THD, phase 1
3867
Float
%A2
Current THD, phase 2
3869
Float
%A3
Current THD, phase 3
3871
Float
NOTE: The PM1200 power meter shows current THD% as ---- in the display and -999.0 in
communications during the following conditions.
When the secondary current is ≤ 0.49 A or ≥ 5.4 A.
When the frequency is > 65 Hz
Energy
FwdVAh
Forward apparent energy
3959
Float
FwdWh
Forward active energy
3961
Float
FwdVARh
Forward reactive inductive
energy
3963
Float
FwdVARh
Forward reactive capacitive
energy
3965
Float
RevVAh
Reverse apparent energy
3967
Float
RevWh
Reverse active energy
3969
Float
RevVARh
Reverse reactive inductive
Energy
3971
Float
RevVARh
Reverse reactive capacitive
Energy
3973
Float
On hrs
1.1.1. On hours
3993
Long
FwdRun secs
Forward run seconds
3995
Long
RevRun secs
Reverse run seconds
3997
Long
Intr
Number of power
interruptions
3999
Long
Demand
Present Demand
Present demand
3975
Float
Rising Demand
Rising demand
3977
Float
Max MD
Maximum demand
3979
Float
Max DM
Occurrence
Time
1.1.2. Maximum demand
occurrence time
3981
Long
Percentage of Load parameters
% Avg Load
Average load percentage
3881
Float
%L1
Percentage of phase 1 load
3883
Float
%L2
Percentage of phase 2 load
3885
Float
%L3
Percentage of phase 3 load
3887
Float
Unbalanced
%Load
1.1.3. Unbalanced %load
3889
Float
Unbalanced %
voltage
1.1.4. Unbalanced % voltage
3891
Float