PLSED309039EN PM1000 Series Power Meters
08/2010 Chapter 6 – Data Communication
© 2010 Schneider Electric. All rights reserved.
Chapter 6: Data Communication
This section is applicable only for PM1200 power meter.
RS 485 Data Port
Data Port advantages:
Rapid, on-line, real time readings into
Your own SCADA software or PLC.
Schneider Electric energy management software products such as ION™
Enterprise, Vijeo Citect, PowerLogic SCADA for pinpointing energy usage
and waste.
Schneider Electric ConPAD: Power meter programming and basic data
reading utility.
Data port has built-in impedance matched design for low reflectance on
long data cables at high Baud rates. Eliminates need for complicated
impedance matching resistors at the ends of long data cables.
Fast 16 ms power meter response, average time to read 10 parameters is
90 to 100 ms (9600 Baud, Even parity, One stop bit).
Direct reading, pre-scaled Float readings. Accurate, full precision low, and
high readings. No need for additional scaling factors or decimal
adjustment.
Fast, easy-to-use grouping of parameters tuned for field requirements.
TURBO area for single point polling (upto 50 per query)
Block area for even faster access to pre-configured data blocks
Installation
Figure 6-1: 2-wire half duplex communication connection
PM1200 power meters rear view
Komentarze do niniejszej Instrukcji