Schneider Electric Multi-Loader Instrukcja Użytkownika Strona 13

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 62
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 12
Other versions: please consult our Customer Care Centre.
Starters with TeSys model U
Type Soft start/soft stop units
Motor power 0.75 to 15 kW
Degree of protection IP20
Reduction of current peaks Yes
Adjustable starting and stopping times 1…10 s
Adjustable breakaway torque
30.... 80% of DOL motor starting torque
Logic inputs 3 logic inputs (start, stop and startup boost)
Logic outputs 1 logic output
Relay outputs 1 relay output
Control supply voltage 24 VDC, 100 mA, ± 10%
References
Soft start/soft stop
units
TeSys starter-controller Power connector
model U
Power base Control unit (1) between ATSU and
TeSys model U
Supply voltage Three-phase 200…480 V
Motor power
230 V 400 V 460 V
Nominal
current (IcL)
kW HP kW HP
0.75 1 1.5 2 6 A ATSU01N206LT LUB12 LUCp05BL VW3G4104
1.1 1.5 2.2/3 3 6 A ATSU01N206LT LUB12 LUCp12BL
1.5 2 5 9 A ATSU01N209LT LUB12 LUCp12BL VW3G4104
4 9 A ATSU01N209LT LUB12 LUCp12BL
2.2 3 5.5 7.5 12 A ATSU01N212LT LUB12 LUCp12BL VW3G4104
3 12 A ATSU01N212LT LUB32 LUCp18BL
4 5 7.5 10 22 A ATSU01N222LT LUB32 LUCp18BL VW3G4104
5.5 7.5 11 15 22 A ATSU01N222LT LUB32 LUCp32BL
7.5 10 15 20 32 A ATSU01N232LT LUB32 LUCp32BL VW3G4104
(1) To compose your reference, replace p in the reference with: «A» for a standard control unit, «M» for a multifunction unit and «B» for an advanced unit.
Dimensions (in mm) width x height x depth
ATSU01 N206LT/N209LT/N212LT 45 x 124 x 130.7
N222LT/N232LT 45 x 154 x 130.7