Installation Instruction 66571764GB3 Fire Detection 25
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
© 2009 Schneider Electric. All rights reserved.
MAINTENANCE 11: (s,c)
Siren control (separate remote LED control) have been configured for
SySe sensor (500 series) but the feature not exist in the sensor (old one)
FAULT 12: (s,c)
Technical alarm input configured for LC address but SW version of LC is
not compatible (> 1.3),
FAULT 13: (s,c/n)
Two or more Apollo devices are at the same address ("double address”).
MAINTENANCE 14:(s,c/n)
Bad scan responses of a device.
MAINTENANCE 15:(s,c/n)
The type ID bits is not compatible with memory ID of Apollo unit
MAINTENANCE 16: (s,c)
Apollo protocol family of device and configuration mismatch
(S90/XP95/Discovery),
FAULT 17: (s,c/n)
Two or more SySeAp devices are at the same address ("double
address”) Yellow LED of units is ON.
FAULT 18: (s,c/n)
Two or more SySeClip and SySeAp devices are at the same address
("double address”).
MAINTENANCE 19:(s,c/n)
“Sub” address of SySeAp multi module overlaps with a some other unit.
FAULT 20: (r)
There is an internal fault in a SySeAp device
MAINTENANCE 21: (r)
A SySeAp device is detached and attached at the loop (powered up)
FAULT 22: (r)
A sub address of multi module is out of the address range (a sub
address would be > 159)
FAULT 51: (r)
Too low analog value received from analog sensor or fault in the internal
operation of an sensor
FAULT 52: (r)
The address does not respond (or bad response)
FAULT 53: (r)
Two or more devices have the same address ("double address”).
FAULT 54: (r)
Break in the input circuit of a monitor module.
FAULT 55: (r)
Break in the output circuit of a control module.
FAULT 56: (r)
Short circuit in output circuit of a control module.
FAULT 57: (r)
The input unit has been configured as "fault input". When the input
alarm activated the FX shows it as fault warning.
FAULT 58: (r)
The input unit has been configured as "zone disablement device" and the
disablement time exceeds (default time 12 hours).
MAITENANCE 59: (r)
The input unit is configured as "maintenance input". When the input
alarms the FX shows it as maintenance warning.
MAINTENANCE 60: (r)
A dirty detector. If the analog value of the detector has exceeded the
maintenance limit for more than 24 hours, this warning is indicated.
If detector exceeds value (during 24h) after user reset this fault warning,
fault warning is re-generated immediately.
Also at case that value of some other detector(s) stay over the
maintenance limit (but 24h timeout has not expired) at the moment when
user select from the menu “report dirty detector” and press “enable” at
access level 3, this fault warning is created.
drift compensation alert of 2251TEM / 7251LASER / OMNI and other
new intelligent sensors. (OMNI / 2251TEM >200 <560; 7251LASER
>200 < 650)
MAINTENANCE 61: (r)
6 months to cell life expiration of CoPTIR sensor
FAULT 62: (r)
Break or short circuit at the conventional sub loop of conventional zone
module.
FAULT 63: (r)
Invalid response from detector (> 4000 µs for normal sensors, >860 and
< 1600 for the OMNI sensor .
Unstable value read from SySeAp device
System Sensor beam detector 6500 in alignment mode.
FAULT 64: (r)
Device type (or functional type ) changed when loop is running.
FAULT 65: (r)
Sensor with separate remote LED control feature is changed to same
type device without this feature. More often this event is indicated with
fault 64
FAULT 66: (r)
Input alarm function is "fault in extinguisher". When module alarms FX
Przeglądanie stron 24