Planning Instruction 66571758GB0 Fire Detection 29
EOL resistor, Exi 4k7, 5%, not Exi 2k94, 1%, not Exi 4k7, 5%, Exi 2k94, 1%, Exi
Max cable resistance 100 100 50 50
Max detector load 1,8 mA 4,0 mA 1,5 mA 3,0 mA
8V 50 – 1000 50 - 550 10 - 700 10 - 320
5V 110 - 1300 110 - 750 150 - 1050 170 - 550
3V 140 - 1500 150 - 880 250 - 1250 280 - 710
1V 180 - 1700 190 - 1010 340 - 1500 380 - 880
0V 200 - 1800 210 - 1070 390 - 1600 440 - 960
7.3 Conventional detection circuit structure and End-of-Line resistors
Each line (conventional detection circuit) of the CLC is terminated with an End-of-Line resistor. The value of this
resistor can be either 4k7 or 2k94, depending on the type of detectors connected to the line and the alarm series
resistor the detector or its base has.
Max 32 detectors and
manual call points
together. The number
may be reduced
further by the current
consumption of the
devices.
See the table in section 7.2 for required series resistors and EOL resistors.
7.4 Con
figurable options
For different applications, the operation of the conventional line can be modified through the configuration tool
WinFX 3NET. See the document 6657 1783GBx FX3Net Configuration Data.
Schneider Electric Pelco Finland Oy
Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571758GB0 49 2011
© 2009 Schneider Electric. All rights reserved.
Przeglądanie stron 28
1 2 ... 24 25 26 27 28 29 30 31 32 33 34 ... 63 64

Komentarze do niniejszej Instrukcji

Brak uwag