Installing Custom Cable Systems
890 USE 100 00
217
D .4 Routing the Cable
Figure 88 shows typical cable drops to several network node devices
and a service access point connector.
Figure 88 Typical Cable Drops
Refer to Figure 88. Route the cable between the site locations of the
network node devices. Guidelines for cable routing are described below.
For dual-cable routing, follow these guidelines for each cable.
V Use a continuous length of cable between locations. Do not use any
kind of taps or splices.
V Two cable segments are routed to each inline drop location: one
segment from the previous drop, and one segment to the next drop.
V One cable segment is routed to the last drop at each end of the
network.