EMC Measures for the Communications Adapter
20
30
A.1 Overvoltage Protection for Remote Bus Lines
(lightning protection)
To protect transmission systems from flashover voltage surges (e.g. lightning),
the remote bus line should be equipped with overvoltage protectors (lightning
arrestors) whenever it is installed outside a building. The nominal discharge
current should be at least 5 kA, for instance by using a type ARE, Cat. Nr. 919 232
made by
Dehn und Söhne, Postfach 1640, 92 306 Neumarkt, Germany
or
Dehn und Söhne, Hans Dehn Str. 1, 92 318 Neumarkt, Germany
Protecting a remote bus cable requires three ARE lightning arrestors per building.