Bulletin No. VVDED397053US Section 1—Hardware Set-Up
November 2000 Connections
© 2000 Schneider Electric All Rights Reserved
9
Figure 5: Male and Female 9-pin SUB-D Connections
Standard RS-485 Bus
Use the following recommendations to construct a standard RS-485 bus:
Use the Phoenix Contact cable (reference IBS RCBxxxM, where
xxx = length of cable in meters).
Maximum length of line: 42,640 ft (13,000 m).
Maximum length of drop cable: 1,312 ft (400 m).
Do not connect more than 256 devices to one bus.
When routing cable, keep the bus away from the power cables (at least
12 in [30.5 cm]), and make any crossovers at right angles.