CANopen TeSys U Motor Control Devices
202
31006709 2/2009
The Multifunction Control Unit
The LUCM Multifunction Control Unit controls, protects and monitors the LUBxx and
LUSxx bases (listed above) and performs the following functions:
Protection
against overcurrent
against thermal overloads, with choice of trip classes from 5 to 30
against ground faults
against phase imbalances
against mechanical jams during or after the start-up phase
against idling
against tripping of the starter via an external signal (as an option)
Warning
The LUCM Multifunction Control Unit includes a warning associated with each of the
above listed protection functions. The warning level can be configured and is
independent from the protection trip level.
Diagnostic
Records and displays:
number of operating hours for the motor
number of starts
number of trips
cause of each trip
For the last five trips, the multifunction control unit records the status of the motor-
starter at the time of the trip (value of currents, thermal status, and trip type).
Preliminary Setup Requirements
Prior to using the Advantys STB Software (ACS) to configure the TeSys U Sc Mu L
on an STB island, you need to set the baud rate, node ID address and assemble the
starter-controller components (see page 178).